❖ Product 
EOG-G01
Modular Type Electro-hydraulic Proportional Reducing Valve
Product details

ORDER CODES

EOG -

G01 -

P

1

Model Name

Thread Connection

Control Port

Pressure Adjusting Range

EOG

G01 : 1/4"

P : P Port

B : B Port

B : 3.1~25.5 kgf/cm2 ( 0.3~2.5 MPa )

1 : 4~71 kgf/cm2 ( 0.4~7 MPa )

2 : 6~143 kgf/cm2 ( 0.6~14 MPa )

 

SPECIFICATION

Model

EOG-G01

Max. Operational Pressure

255 kgf/cm2

( 25 MPa )

Max. Flows

30 l/min

Pressure Adjusting Range

B : 3.1~25.5 kgf/cm2 ( 0.3~2.5 MPa )

1 : 4~71 kgf/cm2 ( 0.4~7 MPa )

2 : 6~143 kgf/cm2 ( 0.6~14 MPa )

Allowable Back Pressure of T port

<25 kgf/cm2 ( <2.5 MPa )

Rated Current

850 mA

Coil Resistance

20Ω ( 20°C )

Magnetic Hysteresis

<3%  <note1>

Amplifier No.

TW2085

Weight

3.6 kg

* Note: Value when a WILSON amplifier TW2085 is used (with dithering).

 

 

HANDLING

1. Air Bleeding : To enable proper pressure control, loosen the air vent when starting up the pump in order to bleed any air from the pump, and fill the inside of the solenoid with hydraulic operating fluid.

2. Manual Pressure Adjusting Screw : For the initial adjustment or when there is no input current to the valve due to an electrical problem or some other reason, valve pressure can be increased by rotating the manual adjustment screw clockwise (rightward). Normally, the manual adjusting screw should be rotated back fully to the left (counterclockwise) and secured with the lock nut.

3. Minimum Control Pressure : Since this valve has an internal drain system, T port back pressure has an effect on minimum control pressure.

4. Load Capacity : Make load capacity (valve OUT side capacity) at least 0.5L.

5. Use an operating fluid that conforms to the both of the following.

Oil temperature: -20 to 70°C.

Viscosity: 12 to 400mm2 /s.

The recommended viscosity range is 15 to 60mm2 /s.